Creating a redundant system

A redundant system with WinCC OA is created via a wizard. Via the wizard you can specify all relevant settings for a redundant project. The wizard is opened via the "New project" button in the project administration (For more information on creating projects via the wizard see chapter Create project). Use the following settings to create a redundant project:

 

Figure: Redundancy configurations when creating a new project

Redundancy-05.gif

 

Choose the project type Redundant project (first redundancy partner) and click on Next >. Another dialog for entering the project data is opened.

 

Redundancy-06.gif

 

Enter a project name, the desired languages and the project path. You can protect the project by specifying a password if necessary. For more information on these settings see chapter Create project. After entering the settings, click on Next >. Another dialog is opened for entering the redundancy specific settings.

 

Redundancy-07.gif

 

The name of the computer the project is created on is automatically shown in the Host 1 text field. Host 2 defines the redundant partner (the button with the network icon opens a "search" dialog, which allows to select the second computer from the network environment. So that the computer name is inserted into the text field at least a directory that is released on this computer has to be chosen). The settings for redundant network connections can be entered in the lower part. If a redundant network connection does not exist disable the check box Redundant network. Thus, the lower part becomes invisible and only Host 1 and Host 2 have to be defined for the redundancy. The text fields are not case sensitive. Note that no double hosts may exist.

note.gifNote

For a redundant network connection two network cards have to be installed per computer. Ensure that the TCP connection and the mapping of the IP addresses to the host names are entered into the "host" file in the "C:/Winnt/system32/drivers/etc/" directory under Windows or into the  "/etc/" directory under Linux. The entry "Hostname-1" is used for the first and the "Hostname-2" for the second network card (this definition has to be entered in the wizard when creating the project - see figure above). The "hosts" file has to be configured on both computers ! For detailed information on the redundant network connections and the configuration of the "hosts" file see chapter Redundant network connections.

caution.gifCaution

The entries in the "hosts" file have to exist also when using a DNS server or local name resolution in order to guarantee a proper functionality of the redundant network connection!

example.gifExample of "hosts" file

 

1.1.1.11     server1     server1-1
1.1.2.11     server1-2

1.1.1.12     server2     server2-1
1.1.2.12     server2-2

 

After entering the settings in the wizard, click on Next >. The last dialog shows all settings.

 

Redundancy-08.gif

 

Click on OK to create the redundant project. If you are not satisfied with the settings you can change the settings of the preceding dialogs via the < Previous button.

 

The above described steps for creating a redundant project with WinCC OA apply for the first redundancy partner. The second computer has to be configured equally with the redundancy settings. The redu project created earlier can be copied to the other computer with the wizard. Choose the following project option (the following steps have to be executed on the second computer for the redundant system):

 

Redundancy-09.gif

 

Click on Next >.

 

Redundancy-10.gif

 

Choose the source path of the redundant project of the first computer via the "Search directory" dialog. The target path is entered automatically into the text field below (since the both projects of the redundant systems have to be saved in the same directory with the same project name). If the target path is not available on the second computer it is created automatically. Assure that the drive to which the target path refers exists and the writing rights are assigned. Click on Next >.

note.gifNote

Under Windows the project directory has to be exported on the first computer so that the source path of the redundant project can be chosen when copying the project to the second computer!

note.gifNote

Note that both projects for the redundancy have to be located on different computers. Under Windows this is checked when a redundant project is copied. Under Linux a check whether the first project is a local project or if it is located on another host, is not executed (note this when creating and copying a redundant project)!

 

Redundancy-11.gif

 

The last dialog again shows the settings made before. Click on OK in order to copy the project to the redundant partner.

 

Via this steps the redundancy is configured (appropriate entries were made in the config file, all necessary managers with right start type are entered into the console). In a redundant project the start sequence of the single managers has to be the following:

 

Database Manager (WCCILdata)

All Archive Managers (WCCOAvalarch -num 0 until -num...)

Event Manager (WCCILevent)

Control Manager (WCCOActrl -f pvss_scripts.lst)

Redundancy Manager (WCCILredu)

All other project specific managers

note.gifNote

It's very important to stick to the start sequence. The redundancy manager has to be at the end of the start sequence, in the case that the DataBG may be disabled in the config file. Otherwise the following problem may occur:
The starting host accepts the recovery request even though it hasn't finished starting yet. Therefore, the remaining drivers can't be started since the host is already in the recovery mode.

In order to prevent this, the redundancy manager has to be started last or you must ensure that the DataBG is enabled.

 

If a project already exists and this project should be run redundant the necessary config entries and managers should be inserted manually. For details on the config entries for a redundant project see chapter configuration files for redundancy.

caution.gifCaution

Drivers, CTRL and all other managers, which should establish a connection to the local Data/Event manager, convert it to "localhost". Thereby, it is not necessary to configure "-data loaclhost" in a non-redundant project. In a redundant project, it is intended that the managers establish a connection to the local and to the redundant Data/Event manager. Thus, the manager must be started with the option -connectToRedundantHosts or the config entry connectToRedundantHosts = 1 must be set in the specific manager section.

 

After creating and starting the redundant project the error weighting has to be configured so that the right behavior (means switching to the computer with the lower error state - see also failure behavior and switching criteria) is executed properly in case of errors. The settings for calculating the error state are executed in the system overview panel (see also Panel system overview in redundant systems).

 