data
point element |
Type |
Input/Output
(seen
from SINAUT driver) |
Description |
Config.LocalTIMNum |
uint |
Input |
SINAUT
node number of the driver for this connection. This has
been specified in the ST7 configuration of the SINAUT
project. |
Config.LocalRack |
uint |
Input |
S7 rack number of the driver.
This has been specified in the SIMATIC S7 (NetPro) configuration
(see Determination
of the rack numbers, slot numbers and connection resource
IDs). |
Config.LocalSlot |
uint |
Input |
S7 slot number of the driver.
This has been specified in the SIMATIC S7 (NetPro) configuration
(see Determination
of the rack numbers, slot numbers and connection resource
IDs). |
Config.LocalResource |
uint |
Input |
S7 connection resource ID of
the driver. This has been specified in the SIMATIC S7
(NetPro) configuration (see Determination
of the rack numbers, slot numbers and connection resource
IDs). |
Config.RemoteIP |
string |
Input |
IP address of the Master TIM. |
Config.RemoteTIMNum |
uint |
Input |
SINAUT node number of the Master
TIM that is assigned to this connection. This has been
specified in the ST7 configuration of the SINAUT project. |
Config.RemoteRack |
uint |
Input |
S7 rack number of the Master
TIM. This has been specified in the SIMATIC S7 (NetPro)
configuration (see Determination
of the rack numbers, slot numbers and connection resource
IDs). |
Config.RemoteSlot |
uint |
Input |
S7 slot number of the Master
TIM. This has been specified in the SIMATIC S7 (NetPro)
configuration (see Determination
of the rack numbers, slot numbers and connection resource
IDs). |
Config.RemoteResource |
uint |
Input |
S7 connection resource ID of
the Master TIM. This has been specified in the SIMATIC
S7 (NetPro) configuration (see Determination
of the rack numbers, slot numbers and connection resource
IDs). |
Config.Active |
bool |
Input |
Allows to deactivate the communication
to the corresponding Master TIM. Active = TRUE
(1), Inactive = FALSE
(0). |
Config.Timeout |
uint |
Input |
General timeout for connection
establishment to the Master TIM and all connected remote
TIMs in milliseconds. |
Config.GQ.DefaultTimeout |
uint |
Input |
Default
timeout for the general query in milliseconds (default
= 60 seconds). |
Command.GQ |
int |
Input |
Starts a general query for the
specific connection (Master TIM).
-1: executes a general query for all existing nodes.
>=0: execute a general query for a selected node
only. |
Command.SyncTime |
time |
Input |
Sends a telegram for time synchronisation
to the Master TIM with the here specified time. If a zero
time is specified, the local time from the operating system
is sent. |
Command.PermanentConnection.Enable |
uint |
Input |
Number
of the Master TIM to which a permanent connection should
be established. |
Command.PermanentConnection.Disable |
uint |
Input |
Number
of the Master TIM to which a permanent connection should
be cut. |
State.ConnState |
int |
Output |
Indication of the connection
state to the Master TIM. Not connected (0), connected
(1), general query (2), not active (3). |
State.ParametrizedCPUTln |
dyn_uint |
Output |
Indication of all configured
nodes of the Master TIM. |
State.LastError |
int |
Output |
Indication of the last error
occurred for this connection. The meaning of the error
code is displayed in the WinCC OA
log viewer or you can find it in the catalogue file msg\sinaut.cat.
Negative error is caused by an ACCON-AGLink
library fault (the meaning of the specific error can be
seen in the table on page Details