../pvss.htm menu.gif basics.gif

Internal data points of the SINAUT driver

An own internal data point on the internal data point type _SinautConn exists for each configured Master TIM.

The _SinautConn data point type has the following structure:

_SinautConn

data point element

Type

Input/Output

(seen from SINAUT driver)

Description

Config.LocalTIMNum

uint

Input

SINAUT node number of the driver for this connection. This has been specified in the ST7 configuration of the SINAUT project.

Config.LocalRack

uint

Input

S7 rack number of the driver. This has been specified in the SIMATIC S7 (NetPro) configuration (see Determination of the rack numbers, slot numbers and connection resource IDs).

Config.LocalSlot

uint

Input

S7 slot number of the driver. This has been specified in the SIMATIC S7 (NetPro) configuration (see Determination of the rack numbers, slot numbers and connection resource IDs).

Config.LocalResource

uint

Input

S7 connection resource ID of the driver. This has been specified in the SIMATIC S7 (NetPro) configuration (see Determination of the rack numbers, slot numbers and connection resource IDs).

Config.RemoteIP

string

Input

IP address of the Master TIM.

Config.RemoteTIMNum

uint

Input

SINAUT node number of the Master TIM that is assigned to this connection. This has been specified in the ST7 configuration of the SINAUT project.

Config.RemoteRack

uint

Input

S7 rack number of the Master TIM. This has been specified in the SIMATIC S7 (NetPro) configuration (see Determination of the rack numbers, slot numbers and connection resource IDs).

Config.RemoteSlot

uint

Input

S7 slot number of the Master TIM. This has been specified in the SIMATIC S7 (NetPro) configuration (see Determination of the rack numbers, slot numbers and connection resource IDs).

Config.RemoteResource

uint

Input

S7 connection resource ID of the Master TIM. This has been specified in the SIMATIC S7 (NetPro) configuration (see Determination of the rack numbers, slot numbers and connection resource IDs).

Config.Active

bool

Input

Allows to deactivate the communication to the corresponding Master TIM. Active = TRUE (1), Inactive = FALSE (0).

Config.Timeout

uint

Input

General timeout for connection establishment to the Master TIM and all connected remote TIMs in milliseconds.

Config.GQ.DefaultTimeout

uint

Input

Default timeout for the general query in milliseconds (default = 60 seconds).

Command.GQ

int

Input

Starts a general query for the specific connection (Master TIM).

-1: executes a general query for all existing nodes.

>=0: execute a general query for a selected node only.

Command.SyncTime

time

Input

Sends a telegram for time synchronisation to the Master TIM with the here specified time. If a zero time is specified, the local time from the operating system is sent.

Command.PermanentConnection.Enable

uint

Input

Number of the Master TIM to which a permanent connection should be established.

Command.PermanentConnection.Disable

uint

Input

Number of the Master TIM to which a permanent connection should be cut.

State.ConnState

int

Output

Indication of the connection state to the Master TIM. Not connected (0), connected (1), general query (2), not active (3).

State.ParametrizedCPUTln

dyn_uint

Output

Indication of all configured nodes of the Master TIM.

State.LastError

int

Output

Indication of the last error occurred for this connection. The meaning of the error code is displayed in the WinCC OA log viewer or you can find it in the catalogue file msg\sinaut.cat.  Negative error is caused by an ACCON-AGLink library fault (the meaning of the specific error can be seen in the table on page Details on the S7 driver).

 

 

Top Of Page

 

V 3.11 SP1