Internal data point _RK512

The driver notifies its status to the WinCC OA via an internal data point of type _RK512. This data point can also be used for changing the driver settings during runtime. Each driver with driver number num uses the internal data point _RK512_num. The data point _RK512 has the following structure:

_RK512

 

 

AliveSndDp

 

AliveSndTimeout

 

AliveRcvDp

 

AliveRcvTimeout

 

ReadComponent

 

ConnState

 

ErrorSPS

 

ErrorDriver

Table: Meaning of the data point elements.

data point name

Type

Meaning

AliveSndDp

string

Peripheral address for sending Alive messages.

AliveSndTimeout

natural number

Time period in seconds in which Alive messages are sent. A value of 0 disables sending of Alive messages.

AliveRcvDp

string

Peripheral address from which Alive messages are expected. Messages, which can be assigned to this address, are evaluated in no further way by the driver.

AliveRcvTimeout

natural number

Time period in seconds in which the driver waits for messages from the PLC. These can be, but need not be, Alive messages. If no message is received within the specified time, the connection is flagged as broken. A value of 0 disables this procedure.

ReadComponent

string

If a peripheral address is entered here, the corresponding data block is read.

ConnState

boolean

Using this data point the WCCOArk512 driver informs the WinCC OA system whether there is a connection to the PLC . A value of false means it is disconnected, true means connected.

ErrorSPS

natural number

The most recent error code not equal to 0 that was sent by the PLC in an acknowledgement message.

ErrorDriver

natural number

The most recent error code not equal to 0 that was sent by the driver to the PLC in an acknowledgement message.

note.gifNote

For data blocks, the value of "ReadComponent" must also contain a value for the data word, i.e. a full peripheral address. The data word is ignored in this case.