data
point name |
Type |
Meaning |
AliveSndDp |
string |
Peripheral address for
sending Alive messages. |
AliveSndTimeout |
natural number |
Time period in seconds
in which Alive messages are sent. A value of 0 disables sending
of Alive messages. |
AliveRcvDp |
string |
Peripheral address from
which Alive messages are expected. Messages, which can be assigned
to this address, are evaluated in no further way by the driver. |
AliveRcvTimeout |
natural number |
Time period in seconds
in which the driver waits for messages from the PLC. These can
be, but need not be, Alive messages. If no message is received
within the specified time, the connection is flagged as broken.
A value of 0 disables this procedure. |
ReadComponent |
string |
If a peripheral address
is entered here, the corresponding data block is read. |
ConnState |
boolean |
Using this data point
the WCCOArk512 driver informs the WinCC OA
system whether there is a connection to the PLC . A value of false
means it is disconnected, true means connected. |
ErrorSPS |
natural number |
The most recent error
code not equal to 0 that was sent by the PLC in an acknowledgement
message. |
ErrorDriver |
natural number |
The most recent error
code not equal to 0 that was sent by the driver to the PLC in
an acknowledgement message. |