Product |
Model Number | Protocol Revision | Software Version | Firmware Version |
WinCC Open Architecture BACnet |
|
135-2008 |
V 3.11 SP1 |
4.0 |
ETM professional control GmbH A Siemens Company Marktstraße 3 A-7000 Eisenstadt Telephone: +43 2682-741-0 Fax: +43 2682-741-107 E-Mail:info@etm.at |
WinCC OA BACnet is a BACnet-Client for Windows and Linux. It comprises the WinCC OA base product and the WinCC OA BACnet AddOn |
Product |
Device Profile | Tested |
WinCC OA BACnet |
BACnet Operator Workstation (B-OWS) (not complete) |
|
Product |
Supported BIBBs |
BIBB Name |
WinCC OA BACnet |
DS-RP-A |
Data Sharing-ReadProperty-A |
DS-RP-B |
Data Sharing ReadProperty-B |
|
DS-RPM-A |
Data Sharing-ReadPropertyMultiple-A |
|
DS-RPM-B |
Data Sharing ReadPropertyMultiple-B |
|
DS-WP-A |
Data Sharing-WriteProperty-A |
|
DS-WPM-A |
Data Sharing-WritePropertyMultiple-A |
|
DS-COV-A |
Data Sharing-COV-A |
|
DS-COVU-A |
Data Sharing-COV-Unsolicited-A |
|
SCHED-A |
Scheduling-A |
|
T-VMT-A |
Trending-Viewing and Modifying Trends-A |
|
T-ATR-A |
Trending-Automated Trend Retrieval-A |
|
AE-N-A |
Alarm and Event-Notification-A |
|
AE-ACK-A |
Alarm and Event-ACK-A |
|
AE-INFO-A |
Alarm and Event-Information-A |
|
DM-RD-A |
Device Management-ReinitializeDevice-A |
|
DM-DDB-A |
Device Management-Dynamic Device Binding-A |
|
DM-DDB-B |
Device Management-Dynamic Device Binding-B |
|
DM-DOB-B |
Device Management-Dynamic Object Binding-B |
|
DM-DCC-A |
Device Management-DeviceCommunicationControl-A |
|
DM-TS-A |
Device Management-TimeSynchronization-A |
|
DM-UTC-A |
Device Management-UTC TimeSynchronization-A |
|
DM-OCD-A |
Device Management-Object Creation and Deletion-A |
Product |
Object Type |
Tested |
WinCC OA BACnet |
Analog Input |
|
Analog Output |
|
|
Analog Value |
|
|
Binary Input |
|
|
Binary Output |
|
|
Binary Value |
|
|
Multistate Input |
|
|
Multistate Output |
|
|
Multistate Value |
|
|
Calender |
|
|
Device |
|
|
Accumulator |
|
|
Pulse Converter |
|
|
Program |
|
|
Notification Class |
|
|
Schedule |
|
|
Trend Log |
|
Product |
Data Link |
Options | Tested |
WinCC OA BACnet |
BACnet/IP (Annex J) |
Can communicate as a Direct BACnet/IP device Can register as a foreign BACnet/IP device. |
Product |
Segmentation Type |
Supported | Window Size
(MS/TP prdoct limited to 1) |
Tested |
WinCC OA BACnet |
Able to transmit segmented messages |
Yes |
Configurable | |
Able to receive segmented messages |
Yes |
Configurable |
Product |
Static Binding Supported |
Tested |
WinCC OA BACnet |
YES |
Product |
Router Option |
Options | Tested |
WinCC OA BACnet |
Router |
Multiple BACnet/IP, Multiple Ethernet |
Product |
Character Sets supported |
WinCC OA BACnet |
ANSI X3.4 (UTF-8) |
ISO 8859-1 |