Object Type |
Object Type
ID |
Comment |
Accumulator |
23 |
Addition
of impulse data of measurement devices over the time.
Used for balancing, statement and energy performance management
(for interval mass counter see Pulse Converter). |
Analog Input |
0 |
Measurement
(e.g. temperature measurement value)
Corresponds to an analog input
value. |
Analog Output |
1 |
Placement
(e.g. place command for rule valve).
Corresponds to an analog output
value. |
Analog Value |
2 |
E.g. as
result of a calculation. |
Averaging |
18 |
Object
including the statistic functions like minimum, maximum,
average and variant. |
Binary Input |
3 |
Notification
of binary states (e.g. operation, interruption or alarm
notification). |
Binary Output |
4 |
Switch
(e.g. switching command on/off). |
Binary Value |
5 |
E.g. calculated
from a logical function. |
Calendar Object |
6 |
Operating
calendar (e.g. holiday list).
Is manipulated with read and write
property services. Complex properties are written and
read as string values. |
Command |
7 |
Command
for the execution of several predefined activities of
other objects. |
Device |
8 |
General
system parameter for BACnet user description (AS, MBE
or other kits). |
Event
Enrollment |
9 |
General
system parameter for criteria definition for the event
notification via Algorithmic Change Reporting. |
File |
10 |
Object
for data transfer (e.g. program, data storage, archiving). |
Group
|
11 |
Object
for grouping readable properties of arbitrary objects
in the same device.
Is manipulated with read and write
property services. Complex properties are written and
read as string values. |
Life
Safety Point |
21 |
Object
which includes information about the properties for danger
alert applications in the network. |
Life
Safety Zone |
22 |
Object
for summary of danger alert object (e.g. for fire detectors,
fire sections). |
Loop |
12 |
Object
for regulation functions (e.g. PID regulator). |
Multistate Input |
13 |
Notification
of multiple states. The alert states are coded as numbers
(e.g. Alert: Off, state1, state 2, ...). |
Multistate Output |
14 |
Switching,
placement
Output states are coded as numbers
(e.g. switch command: Off, state1, state 2, ...). |
Multistate Value |
19 |
E.g. as
calculated value. |
Notification Class |
15 |
Object
for the time-dependant mapping of alarm and event notifications. |
Program |
16 |
Object
for program controlling in a BACnet device (e.g. load
and start). |
Pulse Converter |
24 |
Object
for impulse conversion for mass counting in defined time
intervals (not used for statement purposes, see Accumulator). |
Schedule |
17 |
Object
for execution of circular activities and definition of
unique exceptions. |
TrendLog |
20 |
Object
for trend recording in a BACnet device. |